GD10P CO2 Infrared Gas Detector
The GD10P-CO2 has been designed with features that provide an effective response to the detection of CO2 in a wide range of industrial environments from boiler plant rooms to offshore petrochemical installations.
The GD10P-CO2 differs from all other point infrared gas detectors, because they utilise silicon based solid-state sources.
The complete optomechanical design and construction is so stable that an ultra fast speed of response can be achieved whilst providing unparalleled service life and detector stability, thus saving on maintenance and service costs.
We offer the longest combined detector and IR source warranty on the market.
Supplied with worldwide hazardous area approvals.
An industry standard HART® interface is used for configuration of special fault levels as well as access to extended maintenance data.
GENERAL | |
Type | Gas detector |
Product | GD10P |
Product code | GD10-P00-23BG-0X*-00 |
Manufacturer | Simtronics |
GAS DETECTOR | |
Type | Point Infrared Gas Detector |
Design principle | IR-absorption, Dual wavelength and dual path |
IR Source | Solid state (SimSource), 50Hz sampling rate, long life – 15 years warranty |
Detected gases | Carbon Dioxide |
Calibrated range | 0 – 100% Volume Carbon Dioxide (CO2) |
Weather protector | Sample flow cell recommended. Sinters, gauzes or hydrophobic filters shall not be used. |
PERFORMANCE | |
Lifetime stability | ±5% FS reading (std) |
Accuracy | ±5% FS between 0-50% reading, ±7% FS between 50-100% reading (std) |
Response time (5s – std) | T20 = 1.0 sec / T50 = 2.5 sec / T90: 6 sec |
Response time (1s – fast) | T20 = 0.3 sec / T50 = 0.7 sec / T90 = 1.6 sec (Configured via HART®) |
Calibration interval | Fixed factory calibrated. No field calibration required. |
ELECTRICAL | |
Power supply | 24V DC, range (18 – 32V DC) |
Power consumption | 140 mA typical |
Cable entry | 2x M20, one entry with Exe plug |
Junction box | Integrated Exe junction box. |
Connection | 0.3 mm2 (22 AWG) – 1.5 mm2 (16 AWG), 3 wires |
Analogue output signal | 0-20mA, max. load impedance 500Ω. |
Fault signalling | Diagnosis signalling in the 0.4 – 3.0mA range. Dirty optics / Early-dirty optics – selectable |
Maintenance interface | HART v6.0 Universal Commands (HART version) |
ENVIRONMENT | |
Storage | -40°C to +70°C (-40°F to 158°F) |
Operation | -20°C to +65°C (-4°F to 149°F) |
Humidity | 100% RH (non-condensing) |
Ingress | IP66 / IP67 DIN 40050 |
RFI/EMI | Complies with EN50081-1 and EN50082-2. |
HOUSING | |
Ex Classification | EEx de IIC T6 |
Material | 316 L stainless steel |
Weight | 2.9 kg (6.4 lbs) |
Dimensions | 264L x 104W x 106H (mm)*10.4 x 4.1 x 4.2 (inches) |
APPROVALS | |
ATEX | Certificate Nemko 07ATEX1438 |
IECEx | Certificate IECEx NEM 07.0006 |
CSA | Certificate 1773527 |
SIL | Certificate TÜV 968/FSP 1186.00/15 |
Other | ABS, INMETRO (UL variant available) |
ACCESSORIES | |
499-811938 | Duct mount flange kit |
499-810874 | Sample flow housing |
499-813397 | Mosquito net |
499-815712 | Sunshade |
Product Sheet GD10P CO2809.33 KB
Operating Manual Handheld Terminal1.63 MB
Operating Manual (Italian)821.74 KB
Operating Manual (Portuguese)811.3 KB